25 questions

MCQ-8A firmware samples a push button in a 1 ms timer interrupt and accepts a new state only after four consecutive samples read the same level. On one press the contacts close, bounce for 9 ms (closed 3 ms, open 3 ms, closed 3 ms), then stay closed. How many press events does the firmware register for that press?
MCQ-1A lab checks two thermometers against a 100.0 °C reference, five readings each. Sensor A: 103.0, 103.1, 102.9, 103.0, 103.0. Sensor B: 98.5, 101.5, 99.0, 102.0, 100.0. A technician must pick one to monitor a process that has to stay within 0.5 °C of 100.0 °C, and may apply a single fixed offset correction to the chosen sensor. Which choice and reasoning is correct?
MCQ-2A 12-bit ADC with a 4.096 V reference digitizes a unipolar 0-4.096 V signal. A strain gauge feeds the ADC through a fixed gain-of-50 amplifier, and the front-end noise sits well under one LSB. What is the smallest change in the strain-gauge output that ideally moves the ADC output by one code?
MCQ-3A data-acquisition board samples at 8 kSPS with no analog anti-alias filter ahead of the ADC. With the sensor quiet, the digitized spectrum shows a strong unexpected tone at 3 kHz. The only known interferer on the input wiring is an 11 kHz source. Which statement is correct?
MCQ-4A 12-bit ADC samples a load-cell signal at 1 MSPS. The signal of interest occupies DC to 1 kHz. The measured noise has two parts: white noise at 4 LSB RMS and a coherent 50 Hz hum at 6 LSB RMS. Firmware averages 256 consecutive samples per reading. What is the noise of each averaged reading?
MCQ-16A 16-bit ADC samples a 0–100 mV pressure sensor. The sensor's ground return shares a 30 mΩ trace with a pump that draws 300 mA. With the pump off the reading is stable; with it on the reading jumps by a fixed amount and stays there. What explains the jump?
MCQ-23A 4–20 mA pressure transmitter with a calibrated range of 0–10.00 bar feeds a PLC analog input. The PLC's 16-bit ADC maps 0–20 mA to 0–65535 counts. The historian logs three signals per sample: the PLC's scaled value in bar, the PLC's raw ADC counts, and the transmitter's HART digital process variable in bar. At a verified steady process condition, one sample reads: PLC scaled value 6.35 bar, raw ADC counts 44564, HART digital PV 6.00 bar. Which conclusion does this sample support?
MCQ-5Each of 400 load cells is calibrated against a 10.000 kg reference mass at 22 °C; offset and gain are stored in flash with the reference certificate ID, the date, and the stated validity: 0–10 kg, 15–30 °C, expanded uncertainty ±0.05 % of reading. One unit reads 2.00 kg for a certified 2.00 kg test mass at 22 °C, but 2.53 kg for the same mass in a −18 °C freezer aisle. What is the correct conclusion?
MCQ-10A 24 V relay coil has L = 1 H and R = 100 Ω, so its steady current is 240 mA. The relay drops out when the coil current falls below 24 mA. A flyback diode is fitted across the coil (treat it as ideal, zero forward drop). How long after the MOSFET turns off does the relay drop out?
MCQ-9A firmware engineer drives a 12 V brushed DC motor from a 24 V rail through a low-side MOSFET using a 20 kHz PWM signal at 30% duty cycle. A colleague measures the motor terminal voltage with a slow averaging multimeter and reads about 7.2 V, then claims the PWM block is acting as a linear regulator. Which statement correctly describes what the PWM is doing in this circuit?
MCQ-11A 24 V brushed DC gearmotor has a measured winding resistance of 1.2 Ω and draws 0.35 A at no load and 6000 rpm. It drives an axis that homes into a hard stop, where the shaft can jam for about 200 ms before the controller backs off. The H-bridge driver is rated 5 A continuous and 8 A peak, and the supply feeds it through a 3 A slow-blow fuse. What does the stall current work out to, and what does that mean for this hardware?
MCQ-6A 3.3 V I2C bus runs at 400 kHz with four devices, 10 kΩ pull-ups, and a measured total bus capacitance of 200 pF. A scope shows the rising edge taking about 1.7 µs to go from 0.3·VDD to 0.7·VDD, and the master intermittently gets NACKs. Fast-mode I2C allows at most 300 ns for that transition. What should the engineer change?
MCQ-7A sensor board carries one 3-axis accelerometer and one 128 Mbit SPI NOR flash (SPI only, no I2C interface). The accelerometer streams a 16-bit sample on each of its three axes at 3.2 kHz and must be read with no sample loss; the flash is read in 4 KiB blocks during firmware updates. The MCU has one SPI controller with four chip-select lines and one I2C controller, and the board has exactly four spare GPIOs. The accelerometer supports SPI at up to 10 MHz and I2C at up to 1 MHz (fast-mode plus), and its I2C address is fixed at 0x68. The board's I2C bus already carries an RTC whose address is also fixed at 0x68. Which wiring lets both peripherals meet their requirements?
MCQ-12A greenhouse heater is driven by a PWM duty cycle d between 0 and 1. Over the working range the greenhouse's steady-state temperature tracks the plant model T = T_ambient + 40 * d, with all temperatures in C. The controller law is d = 0.25 + 0.1 * (30 - T), where 30 C is the setpoint and T is the measured temperature. With the outside air at 20 C the loop holds the greenhouse at exactly 30 C. Overnight the outside air falls to 10 C and nobody touches the controller. Where does the greenhouse temperature settle?
MCQ-19A firmware team ships a 6-DOF arm whose joint controller writes a target PWM duty to a timer register, then reads the register back and logs "joint 3 at 42% duty" as its position telemetry. During a pick-and-place cycle the arm reports all joints at commanded duty while the gripper stalls against a jammed part: the motor driver's overcurrent flag latches, the H-bridge output is disabled, and the encoder count stops changing, yet the log shows the commanded duty for the full 800 ms of the cycle. The team wants the next firmware revision to detect this stall within one 10 ms control tick. Which change to the feedback path actually gives them that detection?
MCQ-17A coolant-temperature sensor is sampled every 10 ms over CAN. Its spec is 0–150 °C, 0.5 °C resolution, and a maximum physical rate of 10 °C/s. One frame arrives with a valid CRC and a fresh timestamp, carrying 132.0 °C; the previous frame, 10 ms earlier, carried 88.0 °C. What should the plausibility monitor do with this frame?
MCQ-13A servo drive closes a position loop at 1 kHz using a 10000-count/rev absolute encoder on an axis limited to 3000 rpm, so no valid 1 ms sample can move more than 500 counts. One frame arrives with a passing CRC but a position delta of 4200 counts. The drive trips after three consecutive invalid samples. What should the drive do with this frame?
MCQ-18A steer-by-wire actuator ECU receives a target-angle frame from the steering sensor every 5 ms over CAN. The control loop runs every 1 ms and drives the actuator from the most recent target. The safety case requires commanded angle to reach 0° within 30 ms of the last valid frame, and the actuator must not resume until the sensor has delivered 3 consecutive valid frames. The bus timeout is 20 ms. The sensor connector works loose and frames stop, with the last target at 12°. What should the ECU do when the timeout expires?
MCQ-15A robot cell's e-stop button is wired to a standard PLC input. The PLC program de-energizes a single contactor to stop the robot. During fault injection, the PLC's output transistor fails shorted and the contactor stays energized after the e-stop is pressed. The robot's measured stopping time is 400 ms, and an operator can reach the hazard in 250 ms. Which change makes the e-stop function meet its safety requirement?
MCQ-14A gantry crane holds a 3 t steel plate 8 m above a walkway on an electromagnet drawing about 40 A of coil current; the hoist brake is spring-applied and releases only when energized. The coil's normal feed runs through the safety PLC's output module, and a monitored standby path to the coil bypasses that module. Mid-lift, the safety PLC finds its two hoist-encoder channels in disagreement, and its safety function must now drive the crane to the safe state for that fault. Which response is that safe state?
MCQ-20A gantry axis retracts its cutting head 30 mm to a safe position when the light curtain trips, and the head must clear the material within 200 ms. A 50 mm/s rate limit sits in the position command path to keep normal cutting moves below a structural resonance. At commissioning the safety retract takes 600 ms and the head is still in the material when the curtain is broken. What is the correct fix?
MCQ-22A remote valve controller accepts a command only if the HMAC verifies, the sequence number is greater than the last accepted one, and the command timestamp is within 3 s of the controller's clock. The last accepted sequence is 500. An attacker intercepts a valid command with sequence 501 that never reached the controller, then replays it 10 minutes later. What does the controller do?
MCQ-24A pressure channel on a reactor coolant loop is sampled at 10 kHz (864 million ADC reads/day). Over a week it reports a valid reading 99.99% of the time. A redundant reference shows that during ramp transients the channel's reported value lags the true pressure by 2.5 s, and for 1.2 s the reported value is outside the trip threshold while the channel still reports 'valid'. The channel's built-in diagnostic reports 'healthy' throughout. Which conclusion about this channel's quality is correct?
MCQ-21A battery-powered sensor node runs a 3.3 V ±10% Cortex-M0+ MCU. The datasheet gives 1.8 V as the minimum CPU operating voltage and 2.7 V as the minimum for flash erase/write. The brown-out detector holds the MCU in reset while VDD is below its threshold, and its threshold is selectable at 1.7, 2.0, 2.5, 2.8 or 3.0 V. The node wakes every 60 s, writes a 32-byte log record to flash, and sleeps. On a near-empty battery, bench testing shows VDD sags to 2.4 V for about 5 ms while the log write is in progress, and field returns show corrupted log pages. Which BOD threshold should the firmware configure?
MCQ-25A valve-actuator board passes its bench suite: the firmware builds, the position sensor reads 4.20 mA at full open, and the PWM drives a 2 A solenoid. In the field, about 1 start in 400, the controller reports 'closed' while the valve is 30% open. The solenoid's current-sense line and the actuator motor's 24 V return share one connector. During the motor's 60 ms, 18 A inrush, the shared return lifts the sense ground by 1.6 V, so the steady 3.0 V sense reading becomes 4.6 V: past the 4.5 V 'closed' latch: for the whole inrush. The bench rig powers the sensor from a separate supply. Which test would have caught this escape before release?